Grupy produktów > Environmental Monitoring > HW group Spider

HW group Spider

active converter between RS-485 and 1-Wire bus.

HW group Spider
5140_16371.png
5140_11962.png
5140_31201.png
5140_31202.png
5140_31203.png
5140_31204.png
  • CechyCechy
  • PrezentacjaPrezentacja
  • Więcej informacjiWięcej informacji
  • PDFPDF
  • Up to 4 Spiders to one Poseidon 2250
  • 2x RJ45 connectors for connecting the RS-485 bus enable daisy-chaining.
  • Inputs 1 to 4 support:
  • Dry Contact (relay output) (RJ11)
  • 1-Wire temperature sensor (RJ11)
  • 1-Wire humidity sensor (RJ11)
  • Power over 485 bus from Poseidon, or from external power supply (barrel connector for external 12V adapter).
  • DIP switch for setting the address on RS-485 bus (sensor ID)
  • Signalization of sensor value being read / dry contact switched
  • Reaction to extremely short dry contact pulses (30 ms).

Spider is an active converter between RS-485 and 1-Wire bus. Connects four input sensors (dry contacts or 1-Wire bus) to Poseidon by the RS-485 bus. Spider units can be daisy chain connected.

Spider makes it easier to connect more sensors over longer distances using the RS-485 bus. Suitable for applications in rooms and larger areas.

  • Up to 4 Spider units can be connected to one Poseidon model 2250.
    • With Spider and S-Hub units it is easy to create flexible installations with up to 50 sensors.


  • Four RJ11 inputs support these sensors:
    • Temp-1Wire (1m / 3m / 10m / Outdoor / Temp-Rack19 / HTemp-Rack19)
    • Humid-1Wire (1m / 3m / 10m / HTemp-Rack19)
    • Input for Dry Contact (Flood / smoke and gasses / voltage and current / motion and position detectors)


ProdGrafik

Application examples

  • Detection of system voltage, UPS function detection, Voltage failure alarm activation, On/Off control, Device restart
  • Enlarging the number of inputs for connection of dry contacts for Poseidon 2250.
  • Gathering values from 19” racks, RS-485 bus runs along the wall.
  • Temperature monitoring in supermarket freezers, RS-485 bus runs along the wall behind the freezers



Input

  • 4x 1-Wire probe (temperature or humidity)
    6 values (at most 2 combined temp/humidity probes can be connected)
  • 4x dry contact



Output

  • RS-485 bus –RJ45 (includes power)
  • Poseidon 2250 supports up to 26 probes or 4 Spider units in total
  • An extra power supply adapter is required to connect two or more Spiders
  • The RS-485 communication bus can be up to 1200m (4000ft) long
  • The last sensor on the RS-485 bus (at the end of the line) must terminate the bus
    (“Bus Mode” jumpers set to LAST)



Ordering

600 273 Spider Connects 4 dry contacts or 1W bus RJ12 sensors to Poseidon RS-485 (RJ45) bus